Insulation R-Value Chart: Complete Guide to Every Material (2026)

R-value measures insulation's resistance to heat flow: higher numbers mean better insulating performance. Closed-cell spray foam tops the chart at R-6.0 to R-7.0 per inch, while standard fiberglass batts deliver R-3.0 to R-3.7 per inch. [1] [2] [3] [4] The 2021 IECC asks for R-30 to R-60 in the attic, R-13 to R-30 in wood-frame walls (or less cavity insulation plus continuous foam), and R-13 to R-38 in floors, depending on climate zone. [5]

Updated November 19, 2026
30 min read
Attic: the 2021 IECC asks for R-30 to R-60
Less heat escapingMore heat escapingIllustration of a winter thermal scan, not a measurement.
  • Closed-cell spray foamR-6.0 – R-7.0
  • Polyiso boardR-5.6 – R-6.5
  • XPS boardR-5.0
  • High-density fiberglass battR-3.7 – R-4.3
  • Mineral woolR-3.7 – R-4.3
  • EPS boardR-3.6 – R-4.4
  • Dense-pack celluloseR-3.6 – R-3.8
  • Open-cell spray foamR-3.5 – R-3.8
  • Standard fiberglass battR-3.0 – R-3.7
  • Loose-fill celluloseR-3.2 – R-3.8
  • Blown-in fiberglassR-2.5 – R-3.0
Labeled R-value per inch at the FTC test temperature, from the cited table on this page. Bar colors follow the thermal scan: cooler means more R per inch.

Table of Contents


Complete R-Value Insulation Chart

The chart below gives each material's labeled R-value per inch at a 75°F mean temperature, the test condition the FTC sets for R-value claims, and what the material puts into a 2×4 and a 2×6 stud cavity. [6] Batt figures are the makers' product labels, spray foam figures come from the ICC-ES evaluation reports, and cellulose figures from the makers' coverage charts. Where field performance commonly diverges from the label (compression, settling, thermal bridging), the notes after the table say so.

MaterialR-Value Per InchR-Value at 3.5" (2×4)R-Value at 5.5" (2×6)Best For
Closed-Cell Spray FoamR-6.0 – R-7.0R-22 – R-26R-35 – R-41Air sealing + insulation in one, limited-depth cavities, basement walls
Polyisocyanurate (Polyiso)R-5.6 – R-6.5n/a (board)n/a (board)Continuous exterior insulation, commercial roofing
XPS Rigid FoamR-5.0 (labeled, 75°F)n/a (board)n/a (board)Below-grade, high-moisture applications
High-Density Fiberglass BattR-3.7 – R-4.3R-15R-21 – R-232×4 and 2×6 walls that need the most R-value a batt gives
Mineral Wool / RockwoolR-3.7 – R-4.3R-13 – R-15R-21 – R-23Fire safety, soundproofing, exterior walls
EPS Rigid FoamR-3.6 – R-4.4n/a (board)n/a (board)Foundation insulation, EIFS, ICFs
Dense-Pack CelluloseR-3.6 – R-3.8R-13R-20 – R-21Wall retrofits (drill-and-fill), older homes
Open-Cell Spray FoamR-3.5 – R-3.8R-12 – R-13R-19 – R-21Attic rooflines, cathedral ceilings, air sealing
Standard Fiberglass BattR-3.0 – R-3.7R-11 – R-13R-17 – R-20New construction walls, attics, cost-sensitive projects
Loose-Fill CelluloseR-3.2 – R-3.8n/a (attic product)n/a (attic product)Attic floors, blowing over existing insulation
Blown-In Fiberglass (Attic)R-2.5 – R-3.0 (75°F, rising with depth)n/a (attic product)n/a (attic product)Attic floors (use thicker depth), irregularly shaped spaces

R-value sources: closed-cell spray foam [1] [2] [7] [8] [9] [10] [11]; open-cell spray foam [12] [13] [14]; polyiso [15] [16] [17] [18] [19]; XPS [20] [21] [22] [23]; EPS (name the type; Type XI is R-3.1) [24] [25]; standard and high-density fiberglass batt [3] [4] [26] [27]; mineral wool [28] [29]; dense-pack cellulose [30] [31]; loose-fill cellulose [32] [33]; blown-in attic fiberglass [34] [35] [36] [37] [38]; shared typical-value table [39]. The 2×4 and 2×6 columns are product R-values in a filled cavity: for spray foam, the R-value each ICC-ES report lists at that depth; for a standard batt at 5.5", R-17 to R-18 is a 6.25" or 6.5" R-19 batt compressed into the cavity and R-20 is a batt made for 5.5". Foam boards go on as continuous sheathing rather than cavity fill, and loose-fill attic products have a different density in a wall, so those cells are left blank. XPS, EPS and polyiso per-inch figures are labeled values at a 75°F mean temperature, and R-value per inch varies with thickness (FTC 16 CFR 460.20).

Insulation R-Value Chart: R-value per inch, and what each material puts in a 2×4 or 2×6 wall. Table image from insulationrvalues.com.
Insulation R-Value Chart, drawn from the cited table on this page. Open it full size to save or share it.

Pro Tip: Don't pick insulation by R-value per inch alone. Blown-in fiberglass has the lowest R-per-inch on this chart, but in an open attic you can pile it as deep as you need: at 16–18 inches it reaches about R-43 to R-54. [36] [34] [37] NREL's cost database prices loose fill (blown fiberglass or cellulose) at R-49 on an attic floor at $1.02–$2.13 per sq ft (median $1.83) installed in an existing home, the lowest median of any insulation it prices for attic floors. [40]

Installed cost by insulation type

What insulation costs depends on its form and where it goes more than on the material. NREL's Residential Efficiency Measures Database (REMDB 2024) prices it that way: batts are one line whether they are fiberglass or mineral wool, and loose fill covers blown fiberglass and cellulose alike. [40] Here is one common job for each form.

Insulation form and jobR-valueInstalled, per sq ft (10th–90th percentile)Median per sq ft
Loose fill (fiberglass or cellulose), attic floor, existing homeR-49$1.02–$2.13$1.83
Batts, attic floor, existing homeR-49$2.71–$5.11$3.37
Batts, stud wall, new constructionR-13$1.16–$2.80$1.37
Open-cell spray foam, stud wall, new constructionR-13$2.28–$6.11$3.98
Closed-cell spray foam, stud wall, new constructionR-13$3.09–$9.14$4.48
EPS board, wall sheathing, new constructionR-5$0.93–$1.96$1.19
XPS board, wall sheathing, new constructionR-5$1.14–$4.31$1.43
Polyiso board, wall sheathing, new constructionR-6$1.11–$1.95$1.51

Source: NREL REMDB 2024, installed cost per square foot of insulated surface, 2023 dollars, national. [40]

At the same R-13 in a stud wall, batts cost the least, then open-cell foam, then closed-cell foam. REMDB gives no price for dense-pack cellulose in walls: it rates that line low on both sample size and fit, so this site leaves it out. [40] For your own area, R-value and home, use the insulation cost calculator; the attic insulation cost and spray foam cost guides go further.


What Fits in Your Wall Cavity

Stud cavity depth determines your maximum R-value. Here's what each material delivers in standard framing:

MaterialR-Value in 2×4 (3.5")R-Value in 2×6 (5.5")R-Value in 2×8 (7.25")
Closed-Cell Spray FoamR-22 – R-26R-35 – R-41≈R-46 – R-54 (extrapolated)
Polyiso Board*R-19.6 – R-22.8R-30.8 – R-35.8R-40.6 – R-47.1
XPS BoardR-17.5R-27.5R-36.3
Mineral Wool BattR-13 – R-15R-21 – R-23R-30
High-Density FiberglassR-15R-21 – R-23≈R-30 (compressed)
Dense-Pack CelluloseR-13R-20 – R-21≈R-26 – R-28 (extrapolated)
Open-Cell Spray FoamR-12.3 – R-13.3R-19.3 – R-20.9R-25.4 – R-27.6
Standard Fiberglass BattR-11 – R-13≈R-18 (R-19 batt compressed)≈R-23.6 (R-25 batt compressed)

*Polyiso is rarely installed in stud cavities — it's primarily used as exterior continuous insulation. Values shown for comparison purposes. Spray-foam depths above 5.5" are per-inch extrapolations with no ESR value. Cavity R-values come from product label ratings. [1] [7] [8] [2] [16] [41] [17] [15] [3] [26] [28] [30] [12] [13] [14] [42] [38]

With batts, a 2×4 wall tops out at R-15 (high-density fiberglass or mineral wool); closed-cell spray foam reaches R-22 to R-26. [3] [28] [1] [2] To exceed that, you often add continuous insulation on the exterior. The errata-corrected 2021 IECC Table R402.1.3 lets walls in climate zones 4 through 8 comply with R-30 cavity insulation alone, or R-20 cavity plus R-5 continuous, or R-13 cavity plus R-10 continuous, or R-0 cavity plus R-20 continuous. Continuous insulation is one compliance path, not a blanket requirement. A 2×4 or 2×6 cavity fill alone falls short of R-30, which is where exterior continuous foam earns its place. The 2024 IECC keeps the same wall assemblies. [5] [43]

Use our R-value calculator to model your exact wall assembly, including framing, sheathing, and air films.

When R-value per inch matters most

R-value per inch decides the choice in two situations; outside them it shouldn't drive it:

Limited cavity depth. When you're insulating an existing 2×4 wall, you have exactly 3.5 inches to work with. [42] [38] Closed-cell spray foam gives you R-22+ in that space; standard fiberglass gives you R-11 to R-13. That's a real difference. Same story for cathedral ceilings with 2×8 or 2×10 rafters — you need to hit R-30 or R-38 in limited depth, which rules out low-R-per-inch materials.

Retrofit constraints. Adding insulation to a finished wall without tearing off drywall or siding means working within fixed dimensions. Dense-pack cellulose at R-3.6–R-3.8/inch fills the cavity through small holes. In a 2×4 wall, that yields about R-13. [31] [30] To get more, you'd need to add continuous insulation on the exterior during a re-siding project. See our wall insulation guide for retrofit strategies.

When depth is not constrained (open attics, unfinished basements with framed walls), R-per-inch becomes far less important than cost per R-value.

Pro Tip: If you're re-siding your house anyway, that's the perfect time to add 1–2 inches of continuous rigid foam over the sheathing. How much R-value it adds depends on the foam (at the 75°F label): 1–2 inches of EPS gives R-3.6 to R-8.8, XPS R-5 to R-10, polyiso roof board R-5.6 to R-11.4, and foil-faced polyiso R-6.0 to R-13.1. It breaks thermal bridges, and NREL's REMDB 2024 prices R-5 of EPS added to an existing wall at $1.00–$2.03 per sq ft (median $1.26) (2023 dollars). [40] [20] [24] [21] [15] [17] [19]


Thickness Required for Common R-Values

How many inches of each material reach the common R-value targets, from the makers' labels and coverage charts and the ICC-ES reports:

Inches for R-49

  • Closed-cell spray foam7"–8.2"
  • Polyiso board7.5"–8.8"
  • XPS board9.8"
  • Mineral wool11.4"–13.2"
  • Fiberglass batt13.5"–14"
  • Open-cell spray foam12.9"–14"
  • Blown cellulose13.3"–14.5"
  • Blown fiberglass16.4"–18.25"
Thickness for R-49 from the cited table on this page. Bar colors follow R per inch: cooler means more, so less depth.
Target R-ValueFiberglass BattBlown CelluloseBlown FiberglassMineral WoolClosed-Cell Spray FoamOpen-Cell Spray FoamXPS BoardPolyiso Board
R-133.5"3.6"–4.05"4.75"–5.25"3"–3.5"1.9"–2.2"3.4"–3.7"2.6"2"–2.3"
R-196.25"–6.5"5.3"–5.7"6.75"–7.5"4.4"–5.1"2.7"–3.2"5"–5.4"3.8"2.9"–3.4"
R-309.5"–10.25"8.3"–8.9"10.4"–11.5"7"–8.1"4.3"–5"7.9"–8.6"6"4.6"–5.4"
R-3812"–12.5"10.4"–11.25"13"–14.5"8.8"–10.3"5.4"–6.3"10"–10.9"7.6"5.8"–6.8"
R-4913.5"–14" (single batt)13.3"–14.5"16.4"–18.25"11.4"–13.2"7"–8.2"12.9"–14"9.8"7.5"–8.8"
R-602 stacked batts16.1"–17.7"19.75"–21.75"14"–16.2"8.6"–10"15.8"–17.1"12"9.2"–10.7"

Fiberglass batt: a single R-49 batt is 13.5"–14" (high-density); there is no single R-60 batt, so R-60 uses two stacked layers (for example R-30 + R-30). Blown fiberglass and blown cellulose depths are manufacturer installed (settled) minimums; dry loose-fill cellulose charts already build in about 10% settling, so filling to the chart's initial depth lands at the labeled, settled R-value. XPS depths use the R-5.0/in label; mineral wool, closed-cell, open-cell and polyiso depths divide the target by the per-inch range in the chart above (R-3.7–4.3, R-6.0–7.0, R-3.5–3.8 and R-5.6–6.5). [3] [4] [35] [34] [36] [37] [32] [31] [44] [45] [46] [28] [29] [2] [1] [47] [8] [20] [16] [41] [17] [15]

For complete product-specific thickness data (like which fiberglass batt SKU fits which cavity), see our insulation thickness chart.


R-Value Requirements by Location

The 2021 International Energy Conservation Code (IECC) sets minimum R-values by climate zone. Your local jurisdiction may adopt these directly or modify them, and adoption varies by state, so check with your building department. Energy Star's Seal and Insulate guide covers retrofit priorities.

2021 IECC Minimum R-Value Requirements

Climate ZoneCeiling/AtticWood Frame WallFloorBasement WallExample Cities
1R-30R-13 or R-10ciR-13Not RequiredMiami, Honolulu, Key West
2R-49R-13 or R-10ciR-13Not RequiredHouston, Phoenix, Dallas, New Orleans
3R-49R-20 or R-13+5ci or R-15ciR-19R-5ci or R-13Atlanta, Las Vegas
4 (not Marine)R-60R-30 or R-20+5ci or R-13+10ci or R-20ciR-19R-10ci or R-13NYC, Washington DC, St. Louis
5 and Marine 4R-60R-30 or R-20+5ci or R-13+10ci or R-20ciR-30R-15ci or R-19 or R-13+5ciChicago, Denver, Pittsburgh
6R-60R-30 or R-20+5ci or R-13+10ci or R-20ciR-30R-15ci or R-19 or R-13+5ciMinneapolis, Burlington, Helena
7–8R-60R-30 or R-20+5ci or R-13+10ci or R-20ciR-38R-15ci or R-19 or R-13+5ciAnchorage, Fairbanks

"ci" = continuous insulation — rigid foam or spray foam applied over the exterior of the framing to reduce thermal bridging. "R-13+5ci" means R-13 cavity insulation plus R-5 of continuous exterior insulation, and "R-20ci" means continuous insulation with no cavity fill. Values follow the errata-corrected 2021 IECC Table R402.1.3. [5] [43] The CZ4 (not Marine) wall options are unchanged in the 2024 IECC. In the 2024 IECC the ceiling minimums revert to R-30 in zones 0–1, R-38 in zones 2–3 and R-49 in zones 4–8. Example cities are drawn from the 2021/2024 IECC county table. [48] [49] [50]

Energy Star Retrofit Recommendations

Already have some insulation? Energy Star provides separate guidance for adding to existing insulation vs. starting from scratch:

Climate ZoneAttic (Uninsulated)Attic (add over 3–4" existing)Floor
1R-30R-25R-13
2R-49R-38R-13
3R-49R-38R-19
4A, 4BR-60R-49R-19
4C, 5, 6R-60R-49R-30
7, 8R-60R-49R-38

Source: ENERGY STAR recommended insulation levels. [51]

Use our climate zone map to find your zone, then reference the R-value requirements by ZIP code for your state-specific amendments.


How to Read This Chart

If you're new to insulation, the chart above can look overwhelming. Here's what the numbers actually mean.

R-value per inch is a rate — how much thermal resistance one inch of the material provides. This is how you compare materials on an apples-to-apples basis. The chart above ranks them, and what fits in a wall cavity turns the rate into the R-value a 2×4, 2×6 or 2×8 holds.

Total R-value is what actually matters for your building. It's R-per-inch multiplied by the thickness you install. A 2×4 wall cavity is 3.5 inches deep, so standard fiberglass batt (~R-3.14 per inch) delivers about R-11 in that cavity. A 2×6 cavity is 5.5 inches deep: standard batt at R-3.14 per inch gives about R-17.3, and a 6.25-inch R-19 batt compressed into the 5.5 inches delivers about R-18. To get a full R-19 or more in a 2×6, use a 5.5-inch product such as R-20, R-21 or R-23. [38] [26]

Installed cost has its own table under the chart because its source, NREL's REMDB 2024, prices insulation by form and place rather than by material: a national price per square foot of insulated surface, labor and material together, in 2023 dollars, from the 10th to the 90th percentile. REMDB names what moves a price for each line, such as local wages, drive time and local code requirements. [40]

R-values add up across layers. Along the center of the cavity, R-13 cavity insulation, R-5 continuous exterior foam, R-0.45 for drywall, R-0.63 for 1/2-inch plywood sheathing, and R-0.85 for air films sum to about R-19.9, so "≈R-20" is right only as a center-of-cavity figure. [52] [53] Counting the studs, the same 2×4 wall with R-13 cavity plus R-5 ci framed 16 inches on center is R-17.3 clear-wall (studs included). [54] [55] [42] Our R-value calculator does this math for you. ORNL's online whole-wall calculator is no longer live; its method is now documented in a paper, ORNL's Whole-Wall Thermal Performance Calculator. [56] [57]

For a full explanation of what R-value means and the physics behind it, see What Is R-Value?.


R-Value by Application: What Goes Where

Not every material works in every location. Typical choices by part of the house:

Attic (Flat Ceiling / Attic Floor)

Target: R-49 to R-60 (climate zones 4–8)

Best options: blown-in cellulose or blown-in fiberglass to the required depth. In two makers' coverage charts, dry loose-fill cellulose settles to about 13.5 to 14.5 inches for R-49 and 16.4 to 17.7 inches for R-60. [32] [31] Blown-in fiberglass at about R-2.6 per inch needs roughly 18 inches for R-49. [34] [35] [37] [38]

For a 1,500 sq ft attic floor in an existing home, NREL's REMDB 2024 prices blown-in loose fill at R-49 at $1,525–$3,197 (median $2,738) installed, in 2023 dollars. [40] See our attic insulation cost guide for detailed pricing.

Walls (New Construction)

Target: R-13 to R-30, or less cavity insulation plus continuous foam (2021 IECC, depending on zone)

Standard approach: fiberglass or mineral wool batts in the stud cavity, plus continuous rigid foam on the exterior in zones 5+. A 2×6 wall with an R-21 high-density fiberglass batt plus R-5 polyiso on the exterior reaches about R-22.8 clear-wall (studs included), well above code for most zones. [42] [54] [58]

Walls (Retrofit)

Target: Match the cavity (typically R-13 in 2×4; in 2×6, an R-20, R-21 or R-23 5.5-inch product, since a 6.25-inch R-19 batt compressed into 5.5 inches delivers about R-18) [26] [38]

Best option: dense-pack cellulose blown in through small holes drilled in the siding or interior plaster. At R-3.6 to R-3.8 per inch, it fills a 2×4 cavity to R-13 and a 2×6 cavity to R-20 or R-21. [30] [31] Read our wall insulation guide for the full retrofit process.

Basement Walls

Target: R-10ci to R-19 (zones 4–8)

Best options: Closed-cell spray foam directly on the concrete, or rigid foam board (XPS or EPS) with a framed wall over it. In the makers' ICC-ES reports, 2 inches of closed-cell foam is R-12 to R-14 and 3 inches is R-19 to R-22. [1] [7] [2] Closed-cell foam is typically a Class II vapor retarder, so it also slows moisture from the concrete. [39] See our basement insulation guide.

Crawl Space / Floor Over Unconditioned Space

Target: R-13 to R-38 (depending on zone)

Conditioned crawl spaces: insulate the walls with rigid foam or spray foam. Unconditioned: insulate the floor above with fiberglass batts (R-19 or R-30 faced batts between floor joists) or spray foam on the underside. Check our crawl space guide for the full breakdown.

Floor batts can sag away from the subfloor over time and leave an air gap under it. If you go the batt route, hold them up with insulation support wires (tiger teeth). Spray foam on the underside of the subfloor doesn't sag, and it air seals the floor as well. NREL's REMDB 2024 prices R-30 batts in a crawl space ceiling at $2.37–$4.38 per sq ft (median $2.82) installed in an existing home, and closed-cell foam at R-15 on the walls of a conditioned crawl space at $4.03–$11.92 per sq ft (median $5.84), counted per square foot of wall, in 2023 dollars. [40] A crawl space's walls usually have less area than its floor, so compare totals for your own dimensions in the cost calculator.

Roof (Cathedral Ceilings / Vaulted Ceilings)

Target: R-30 to R-49 (depending on zone and assembly type)

Cathedral ceilings are one of the hardest assemblies to insulate well because you're working within a fixed rafter depth, typically 2×8 (7.25") or 2×10 (9.25"), with no accessible attic space above. A 2×10 rafter filled with fiberglass gives you about R-30, which falls short of the R-49 or R-60 ceiling requirement in zones 4+. [38] [3]

Three approaches work here. First, open-cell spray foam sprayed directly on the underside of the roof deck fills the full rafter depth and air seals simultaneously: 5.5 inches in a 2×6 gives R-19 to R-21, while 9.25 inches in a 2×10 delivers R-32 to R-35. [8] [12] [13] [14] Second, a hybrid approach: closed-cell spray foam on the roof deck (2 inches for R-12 to R-14 plus air/vapor barrier) with the remaining cavity filled with dense-pack cellulose or fiberglass batt. [1] [7] [2] Third, rigid foam installed above the roof deck during a re-roof, which adds R-value without eating into rafter depth — 3 inches of polyiso roof board above the sheathing adds about R-17.4, its long-term (LTTR) value (derate for cold climates). [41] [15] [16]

Floor Over Garage

Target: the IECC floor value for your zone, R-13 to R-38 (2021 IECC)

The floor above an attached garage needs insulation for energy and gypsum board for fire separation. A typical approach: R-19 or R-30 unfaced fiberglass batts between the floor joists, held up with insulation wires. Under a habitable room, the 2021 IRC (Table R302.6) requires at least 5/8" Type X gypsum board or equivalent on the garage side. [59] Spray foam on the underside of the subfloor seals air better: 2 inches of closed-cell gives R-12 to R-14 plus an air barrier, and batts can fill the rest of the joist depth toward R-30. [1] [7] [2] An air-sealed floor also keeps garage exhaust out of the rooms above.


Why R-Value Isn't Everything

An R-38 attic can perform worse than a well-sealed R-19 attic. The label R-value is tested in a lab at 75°F mean temperature with zero moisture and perfect installation. Your house is not a lab. [60] [6]

Three factors that kill real-world performance:

1. Air Leakage Insulation slows conductive heat transfer. It does almost nothing to stop air carrying heat through gaps, cracks, and penetrations. ENERGY STAR estimates that air sealing together with adding insulation saves an average of 15% on heating and cooling costs (about 11% of total energy costs), ranging from 7% to 20% of heating and cooling by climate zone. No source gives a figure for air sealing on its own, but skipping it leaves much of that saving on the table. [61] [62] [63]

2. Installation Quality RESNET grades insulation installation from Grade I (careful fill, no gaps, no compression) to Grade III (visible gaps, voids, compression). Gaps and voids measurably cut performance. In ORNL hot-box tests of a 2×6, 24-inch-on-center wall with R-19 batts, a careful install measured R-15.4 while a worst-typical install with rounded batt shoulders, 2% voids and inset stapling dropped to R-13.2, a 14% loss. A Johns Manville study for the U.S. Navy found that a 4.2% uninsulated area cut an R-19 ceiling's resistance by 34%. BRANZ hot-box tests found that 16 mm edge gaps cut a wall's R-value by 35%. [64] [65] [66]

3. Thermal Bridging Wood framing conducts heat about 2.4 to 3.4 times faster than the insulation between it. Softwood runs about R-1.25 per inch against cavity insulation at R-3.0 to R-4.3 per inch. [67] [53] In a standard 2×6 wall framed 16 inches on center, 23–25% of the wall area is lumber. [54] [52] That thermal bridging drops a cavity R-23 wall to about R-17.8 clear-wall (studs included). The fix: continuous insulation over the framing, which covers both studs and cavities. Adding R-5 of exterior foam to a 2×6 R-21 wall lifts it from about R-17.0 to about R-22.8 clear-wall, roughly the full R-5. [42] [55]


Temperature Effects on R-Value

Not all insulation performs the same in every climate. FTC rules require manufacturers to test R-value at a 75°F mean temperature (using ASTM C177 or C518), but your attic in Minnesota doesn't stay at 75°F. [6] [68] [60]

MaterialR/Inch at 75°FR/Inch at 25°F MeanR/Inch at 40°F MeanTemperature Sensitivity
PolyisoR-5.56R-4.05 (−27%)R-4.91 (−12%)High — loses R-value as it gets colder
XPSR-5.0R-5.6R-5.4Improves in cold (+8% at 40°F, +12% at 25°F)
EPSR-3.9 – R-4.2R-4.4 – R-4.8R-4.2 – R-4.6Improves in cold (+8–10% at 40°F, +13–14% at 25°F)
FiberglassR-3.0 – R-4.3higher than at 75°Fhigher than at 75°FR rises as mean temp falls
Mineral WoolR-3.7 – R-4.3not givennot givenThe cited makers' sheets give no cold-temperature R-values
CelluloseR-3.2 – R-3.8not givennot givenThe cited makers' sheets give no cold-temperature R-values

Polyiso cold-temperature values are NRCA's 2014 test data for 2-inch roof boards (R-5.56/in at 75°F, R-4.91 at 40°F, R-4.05 at 25°F mean) as published in NRCA's Professional Roofing (March 2015); Building Science Corporation Info-502 publishes the same trend as curves only. XPS and EPS cold values from manufacturer data; fiberglass direction from ORNL and NBS test work. At a 25°F mean, Type II EPS (about R-4.8) outperforms polyiso (about R-4.05). [69] [70] [71] [21] [72] [73] [24] [46] [74] [75] [4] [28] [32]

Polyisocyanurate (polyiso) is the biggest offender. It's rated R-5.6 to R-6.5 per inch at 75°F. [15] [16] [17] NRCA testing of 2-inch polyiso roof boards (published in Professional Roofing, March 2015) measured R-5.56 per inch at a 75°F mean, R-4.91 per inch at 40°F (down 12%) and R-4.05 per inch at 25°F (down 27%). Building Science Corporation's Info-502 publishes temperature curves but no per-temperature numbers, so that document does not support a specific percentage. If you're in zone 5 or higher and using polyiso on the exterior, derate it or layer it with XPS or EPS. [69] [70]

XPS foam board performs slightly better in cold temperatures — its R-value per inch rises a little as temperature drops. [73] Long-term behavior depends on the product generation, and the evidence is trade-funded on all sides. Legacy HCFC-blown XPS averaged about 7–10% below its 180-day value over the long term (roughly R-4.5–4.65 from R-5.0) as blowing agent escaped. Owens Corning's current FOAMULAR NGX lists R-5.0 per inch as its long-term (LTTR) value and warrants at least 90% retention; DuPont states a long-term R-5 per inch. [76] [21] [23]

EPS foam board gains R-value as it gets colder. Atlas ThermalStar Type XIV EPS is rated R-4.4 per inch at a 75°F mean, R-4.8 at 40°F and R-5.0 at 25°F, which makes EPS a good cold-side partner for polyiso. [77]

Fiberglass also gains a little R-value as the mean temperature falls, in ORNL and NBS test work. [46] [74] The mineral wool and cellulose makers' data sheets give no cold-temperature R-values.

Pro Tip: Building Science Corporation's Info-502 recommends either thicker polyiso or a cold-tolerant layer outside the polyiso for cold-climate exterior foam. One version is a "polyiso sandwich" — EPS on the outside (cold side) with polyiso on the inside (warm side), so the polyiso stays warmer and holds more of its R-value while the EPS handles the cold exposure. BSC states this qualitatively and gives no fixed percentage gain. [70]

For a complete analysis, see our individual guides on polyiso, XPS, and EPS.


Common Mistakes

1. Compressing batts to fit. An R-19 batt is 6.25 inches thick. Stuffing it into a 3.5-inch 2×4 cavity doesn't give you R-19 in less space — it gives you approximately R-13. Compression reduces R-value. Use the right product for the cavity: R-13 or R-15 for 2×4, and a 5.5-inch R-20, R-21 or R-23 product for 2×6 (a 6.25-inch R-19 batt compressed into a 2×6 delivers about R-18). See our insulation thickness chart for correct pairings. [3] [4] [38] [27]

2. Ignoring air sealing. Insulation without air sealing is like wearing a sweater with no windbreaker. Seal penetrations, top plates, recessed lights, and duct boots before insulating. Our guide on air sealing vs. insulation explains the priority order.

3. Using the wrong vapor barrier. In cold climates (zones 5+), you generally want a vapor retarder on the warm side of the insulation. In mixed or hot-humid climates, putting poly on the wrong side traps moisture and rots framing. Check our vapor barrier guide before you install faced vs. unfaced insulation.

4. Comparing materials on R-value per inch alone. Closed-cell spray foam at R-6 to R-7 per inch [1] [2] is impressive, but on an open attic floor NREL's REMDB 2024 puts its median at R-38 at $14.74 per sq ft, against $1.47 for blown-in loose fill at the same R-value (2023 dollars, existing home). [40] Compare total R-value for your application, then compare cost.

5. Not accounting for settling. Dry loose-fill cellulose settles about 10% (stabilized cellulose much less, roughly 1–6%). You don't have to add your own allowance: manufacturer coverage charts already give the initial installed depth that settles to the labeled R-value, which the FTC rates at settled density (16 CFR 460.5). For R-49, dry loose-fill charts give an initial depth of about 15.0 to 16.1 inches, settling to roughly 13.5 to 14.5 inches. Follow the bag chart for the product you buy. [32] [44] [31] [46] [6] [78]


Key Takeaways

  • Closed-cell spray foam delivers the highest R-value per inch (R-6.0–R-7.0), but blown-in cellulose and fiberglass offer the best value for open spaces like attics where thickness isn't constrained.
  • Homes in zones 4–8 need R-60 in the attic per the 2021 IECC. R-49 counts for R-60 only on the prescriptive R-value path, and only when it covers 100% of the ceiling area and the full-height, uncompressed R-49 extends over the wall top plate at the eaves. Walls there need R-30 in the cavity, R-20+5ci, R-13+10ci or R-20ci, and floors R-19 to R-38 depending on zone. [5]
  • R-value is only part of the picture — air sealing, installation quality, and thermal bridging can make or break actual performance.
  • R-values add up across layers: cavity insulation + continuous insulation + sheathing + drywall + air films all contribute.
  • Polyiso R-value drops significantly in cold temperatures — derate it in climate zones 5+ or pair it with EPS/XPS.
  • Always match insulation thickness to cavity depth. Compressing batts wastes money and R-value.
  • With batts, a 2×4 wall tops out at R-15; going higher takes closed-cell spray foam (R-22 to R-26) or continuous exterior insulation. [3] [1] [2]
  • ENERGY STAR estimates that sealing and insulating together save an average of 15% on heating and cooling costs (about 11% of total energy costs; 7% to 20% of heating and cooling by climate zone). [62] [63]

FAQ

What R-value do I need for my home?

It depends on your climate zone and which part of the house you're insulating. The 2021 IECC requires R-30 to R-60 for attics, R-13 to R-30 for wood-frame walls (or a cavity-plus-continuous combination such as R-20+5ci), and R-13 to R-38 for floors, scaling with colder climates. [5] Use our R-value calculator to determine your specific needs: enter your ZIP code, assembly type, and existing insulation to get a personalized recommendation.

Do R-values add up when you stack insulation?

Yes. R-values are additive across layers. If you have R-19 existing attic insulation and blow R-30 on top, you get R-49 total. This works across different materials too: R-13 fiberglass cavity insulation plus R-5 continuous exterior polyiso gives you R-18 of insulation, plus about R-1.9 more from drywall (R-0.45), 1/2-inch plywood sheathing (R-0.63) and air films (R-0.85), measured through the cavity. [52] [53] See What Is R-Value? for how assemblies add up.

What insulation has the highest R-value?

Closed-cell spray foam leads at R-6.0 to R-7.0 per inch. Polyiso rigid foam is close behind at R-5.6 to R-6.5 per inch (at 75°F). [1] [2] [15] [17] The chart at the top of this page ranks every material. Keep in mind that the highest R-per-inch isn't always the best choice. It's often the most expensive, and on an open attic floor, blown-in loose fill at greater depth reaches the same total R-value for a fraction of what closed-cell foam costs. [40]

Is higher R-value always better?

More R-value is always better at resisting heat flow, but there's a point of diminishing returns. Going from R-0 to R-19 in an attic is large: it cuts heat loss through the ceiling by about 90 to 94%. Going from R-19 to R-38 saves roughly half again. [52] [42] [53] [54] Going from R-38 to R-60 adds a smaller improvement again, because each added R-value cuts a smaller remaining heat flow. A sensible order: air seal first, reach at least the code minimum, then go above it in the attic if the budget allows.

How much R-value can I fit in a 2×4 wall?

A 2×4 stud cavity is 3.5 inches deep. The maximum cavity R-values are: R-22 to R-26 with closed-cell spray foam, R-15 with high-density fiberglass, R-15 with mineral wool, R-13 with standard fiberglass or dense-pack cellulose. To exceed R-15 without spray foam, add continuous rigid foam insulation on the exterior of the wall. [3] [28] [30]

Does R-value per inch change over time?

For most materials, little changes if they stay dry and uncompressed. Fiberglass, mineral wool, and EPS hold their R-per-inch over time, though registry sources do not include long-term field settling studies for batts. XPS is the one that depends on blowing agent and product generation: legacy HCFC XPS drifted roughly 7–10% below its 180-day value long term (about R-4.5–4.65 from R-5.0), while current FOAMULAR NGX publishes an LTTR (CAN/ULC S770) of R-5.0/in and warrants at least 90% retention, and DuPont states a long-term R-5 per inch. That LTTR is determined under CAN/ULC-S770, not by ASTM C578 (C578 values are 180-day aged). The evidence on both sides is trade-funded, so treat a single aged number with caution. [76] [21] [23] Cellulose doesn't lose R-per-inch. Dry loose-fill cellulose charts build in about 10% settling, and the labeled R-value is rated at settled density under FTC rules (16 CFR 460.5), so an attic filled to the chart's initial depth reaches its labeled R-value. [32] [46] [6]

How thick is R-30, R-38, and R-49 insulation?

It depends on the material. R-30 takes about 8.3 to 8.9 inches of settled blown cellulose, 10.4 to 11.5 inches of blown fiberglass or a 9.5- to 10.25-inch fiberglass batt. R-38 takes 10.4 to 11.25 inches of cellulose, 13 to 14.5 inches of blown fiberglass or a 12- to 12.5-inch batt. R-49 takes 13.3 to 14.5 inches of cellulose, 16.4 to 18.25 inches of blown fiberglass, a single 13.5- to 14-inch high-density batt, or 7 to 8.2 inches of closed-cell spray foam. [3] [4] [32] [31] [44] [45] [34] [35] [36] [37] [2] [1] [11] The thickness table covers eight materials from R-13 to R-60, and the thickness calculator works out any target.

Sources

  1. ICC Evaluation Service (holder: Huntsman Building Solutions, LLC), ICC-ES Evaluation Report ESR-2629 (Foam-Lok FL2000 (closed-cell; aka Air Tight CC, GuardFoam 55 CC, Foam-Lok AB2000)), reissued Dec 2021, revised Jul 2022 (copy on huntsmanbuildingsolutions.com) (retrieved Oct 2026)
  2. ICC Evaluation Service (holder: Huntsman Building Solutions, LLC), ICC-ES Evaluation Report ESR-4073 (Heatlok HFO High Lift (closed-cell, HFO)), reissued Aug 2026 (retrieved Oct 2026)
  3. Owens Corning, PINK Next Gen Fiberglas Insulation Manufacturers Fact Sheet (Pub. 10025109-B, May 2026) (retrieved Oct 2026)
  4. Johns Manville, Fiberglass Manufacturers Fact Sheet (BID-380, 12/19, (c)2019) (retrieved Oct 2026)
  5. International Code Council (ICC), 2021 IECC Errata (complete) - Table R402.1.3 entry, Printings: All, posted 2021-08-10 updated 2026-09-18 (retrieved Oct 2026)
  6. US Federal Trade Commission (16 CFR 460), 16 CFR Part 460 Labeling and Advertising of Home Insulation (FTC R-value Rule), via Cornell LII e-CFR mirror - § 460.5 (retrieved Oct 2026)
  7. ICC Evaluation Service (holder: North American Spray Foam Polymers), ICC-ES Evaluation Report ESR-4484 (EPS 2000 Closed Cell Spray Foam (North American Spray Foam Polymers)), reissued Oct 2022, archived copy (Wayback Machine 2023-05-07); not in the ICC-ES directory as of Nov 2026 (retrieved Nov 2026)
  8. ICC Evaluation Service (holder: SOPREMA Corporation), ICC-ES Evaluation Report ESR-4411 (SOPRA-SPF 201 (closed-cell)), reissued May 2021 (renewal May 2023) (retrieved Oct 2026)
  9. BASF Corporation, Technical Data Sheet - WALLTITE One Series, Rev. 10.08.26 (retrieved Nov 2026)
  10. Huntsman Building Solutions, FOAM-LOK 2000-4G Technical Data Sheet (Spanish-language US sheet), REV 15.12.20 (retrieved Oct 2026)
  11. US Federal Trade Commission (16 CFR 460), 16 CFR Part 460 Labeling and Advertising of Home Insulation (FTC R-value Rule), via Cornell LII e-CFR mirror - § 460.20 (retrieved Oct 2026)
  12. ICC Evaluation Service (holder: Huntsman Building Solutions LLC), ICC-ES Evaluation Report ESR-1826 (Classic Ultra Select (also Classic, Classic Ultra) open-cell), reissued Mar 2026 (renewal Feb 2027) (retrieved Oct 2026)
  13. ICC Evaluation Service (holder: Huntsman Building Solutions, LLC), ICC-ES Evaluation Report ESR-2847 (Foam-LOK FL500 (aka AirTight OC, GUARDFOAM 55 OC, Open Cell Retrofit Foam) open-cell), reissued Sep 2026 (retrieved Oct 2026)
  14. ICC Evaluation Service (holder: Universal Polymers Corporation), ICC-ES Evaluation Report ESR-3803 (UPC 500 half-pound open-cell SPF), reissued May 2022, archived copy (Wayback Machine 2023-05-07); not in the ICC-ES directory as of Nov 2026 (retrieved Nov 2026)
  15. NRCA, Professional Roofing, 'PIMA updates its QualityMark CM program for determining long-term thermal resistance', Mark S. Graham (NRCA), Professional Roofing, Aug 2013 (Tech Today) (retrieved Nov 2026)
  16. Polyisocyanurate Insulation Manufacturers Association (PIMA), PIMA Performance Bulletin #04 'Measuring the R-value of Polyiso Roof Insulation' (footer 5/14; cites 2015 data) (retrieved Oct 2026)
  17. Rmax, Rmax Product Data Sheet THERMASHEATH (foil-faced polyiso), Revision 05-15-2025 (retrieved Nov 2026)
  18. Johns Manville, AP Foil-Faced Polyisocyanurate Continuous Insulation data sheet, BID-0151 (09/26) (retrieved Nov 2026)
  19. DuPont (Performance Building Solutions), DuPont Thermax Sheathing Insulation product page (retrieved Oct 2026)
  20. Owens Corning Foam Insulation, LLC, FOAMULAR & FOAMULAR NGX XPS Insulation: ASTM C578 Types and Physical Properties (Tech Bulletin, Pub. No. 10015702-C, July 2025) reproducing ASTM C578-23 (retrieved Oct 2026)
  21. Owens Corning Foam Insulation, LLC, Product Data Sheet FOAMULAR NGX 250 XPS Insulation, Pub. No. 43522-V, Oct 2025 (retrieved Oct 2026)
  22. Kingspan Insulation LLC, Kingspan GreenGuard GG25-LG XPS Insulation Board product data sheet, v3, 03/2026 (retrieved Nov 2026)
  23. DuPont (Performance Building Solutions), Styrofoam Brand Square Edge Extruded Polystyrene Foam Insulation product page (retrieved Oct 2026)
  24. Atlas Molded Products (division of Atlas Roofing Corp.), ThermalStar E Tech Data sheet (ARC-064 TS E Tech-Data_10.25) (retrieved Nov 2026)
  25. Insulfoam (a Carlisle company), R-Tech I 10 psi Moisture Resistant Insulation technical data sheet (TDS dated 04/30/18) (retrieved Nov 2026)
  26. Owens Corning, PINK Next Gen Fiberglas Insulation Product Data Sheet (Pub. 10024567-J, May 2026) (retrieved Oct 2026)
  27. NAIMA, Insulation Facts #21: High-Performance Batts for Walls and Cathedral Ceilings (BI 467, 7/04) (retrieved Oct 2026)
  28. ROCKWOOL, ROCKWOOL Comfortbatt Thermal Batt Insulation Technical Data Sheet (US), issued 07-2026 (retrieved Oct 2026)
  29. Owens Corning (Thermafiber), Thermafiber Fire & Sound Guard Plus Manufacturers Fact Sheet (Pub. 10027588, Oct 2024) (retrieved Oct 2026)
  30. Greenfiber, SANCTUARY Cellulose Fact Sheet (PM-6.3329 Rev K, 05/26) (retrieved Nov 2026)
  31. Nu-Wool Co., Inc., Nu-Wool 'This Is Cellulose' FTC fact sheet / Pneumatic Application Coverage Chart (05/2016) (retrieved Nov 2026)
  32. Applegate Insulation (Greenfiber), Applegate Loose-fill Cellulose Insulation Fact Sheet (#IFS-ALF26.5-201606-A, (c)2020; RDS-LF9587), archived copy (Wayback Machine 2023-05-25) (retrieved Nov 2026)
  33. Nu-Wool Co., Inc., Nu-Wool Premium Cellulose Insulation product page (retrieved Oct 2026)
  34. Owens Corning, ProPink L77 PINK Fiberglas Loosefill Insulation Manufacturers Fact Sheet (Pub. 22676-O, Dec 2023) (retrieved Oct 2026)
  35. Johns Manville, JM Building Insulation Submittal Form (BID-0028, 9/26) (retrieved Oct 2026)
  36. Knauf Insulation, Knauf Jet Stream ULTRA Blowing Insulation Product Data Sheet (valid from 05/25; (c)2024), linked from knaufnorthamerica.com product page (retrieved Oct 2026)
  37. CertainTeed, CertainTeed InsulSafe SP Fiberglass Blowing Insulation data sheet (Code No. 09-11-4525-US-EN, 10/24) (retrieved Nov 2026)
  38. City of Seattle SDCI (adopts WA State Energy Code App. A), 2021 Seattle Energy Code, Appendix A (Default Heat Loss Coefficients), Table A101.4 R-value of fiberglass batts compressed within various depth cavities (retrieved Oct 2026)
  39. Pacific Northwest National Laboratory / US DOE Building America Solution Center, Typical R-values and Vapor Retarder Classifications for Common Insulation Materials — Building America Solution Center (PNNL for US DOE), updated 2021-12-23 (retrieved Oct 2026)
  40. National Renewable Energy Laboratory (NREL), National Residential Efficiency Measures Database (REMDB) 2024 — machine-readable file REMDB_2024.12.23.xlsx (CC BY 4.0) (retrieved Oct 2026)
  41. Sika Corporation, Product Data Sheet Sarnatherm ISO, Aug 2024, v06.03 (retrieved Oct 2026)
  42. Natural Resources Canada (Government of Canada), NRCan, Tables for Calculating Effective Thermal Resistance of Opaque Assemblies (ENERGY STAR for New Homes; issued 2014-01-02, modified 2025-01-14) (retrieved Oct 2026)
  43. US DOE Building America Solution Center (PNNL), DOE/PNNL Building America Solution Center: '2009-2021 IECC and IRC Minimum Insulation Requirements for New Homes' (updated 2021-09-17) (retrieved Oct 2026)
  44. Applegate Insulation (Greenfiber), Applegate Stabilized Cellulose Insulation Fact Sheet (PM 6.3330 Rev A 09/24, Greenfiber) (retrieved Oct 2026)
  45. Greenfiber, Greenfiber SANCTUARY Defense Attic Card (PM-6.3328-SD Rev C, 03/25) (retrieved Nov 2026)
  46. Oak Ridge National Laboratory (Wilkes & Childs), Thermal Performance of Fiberglass and Cellulose Attic Insulations, ASHRAE/DOE/BTECC Thermal Performance of the Exterior Envelopes of Buildings V (Dec 1992) (retrieved Oct 2026)
  47. Spray Polyurethane Foam Alliance (SPFA), SPFA FAQs page (last modified 2026-04-27) (retrieved Oct 2026)
  48. International Code Council (ICC), 2024 IECC Code and Commentary - sample chapter (3560S24 Sample PDF) (retrieved Oct 2026)
  49. International Code Council (ICC) / State of Colorado model code, Colorado Model Low Energy and Carbon Code - ICC sample excerpt (3800S24CO Sample PDF), Table C301.1 'Climate Zones, Moisture Regimes and Warm Humid Designations by State, County and Territory' (pp. 36-66, all 50 states + DC + territories) (retrieved Oct 2026)
  50. PNNL (Pacific Northwest National Laboratory), Athalye, Taylor, Liu (PNNL), 'Impact of ASHRAE Standard 169-2013 on Building Energy Codes and Energy Efficiency', SimBuild 2016 (copy hosted by NCTCOG) (retrieved Oct 2026)
  51. US EPA ENERGY STAR, ENERGY STAR (US EPA) 'Recommended Home Insulation R-Values' - Recommended insulation levels for retrofitting existing wood-framed buildings (retrieved Oct 2026)
  52. City of Seattle SDCI (Seattle Energy Code, derived from Washington State Energy Code), 2018 Seattle Energy Code, Appendix A Default Heat Loss Coefficients, Sec. A101.3 (retrieved Oct 2026)
  53. California Energy Commission (code text) via Energy Code Ace, California 2013 Title 24 Part 6 Joint Appendix JA4.6 'Physical Properties of Materials' (Table 4.6.1), hosted by Energy Code Ace (CA utility program) (retrieved Oct 2026)
  54. ASHRAE / ANSI / IES, ANSI/ASHRAE/IES Addendum ay to Standard 90.1-2022 (approved 2024-10-31), Normative Appendix A sec. A3.4.1 (retrieved Oct 2026)
  55. City of Saskatoon Building Standards (reproducing NRC National Building Code of Canada 2015), City of Saskatoon Energy Efficiency Handbook (printed July 2019), reproducing NBC 2015 Table A-9.36.2.4.(1)-D (retrieved Nov 2026)
  56. Oak Ridge National Laboratory, ORNL Building Technologies tools page (whole-wall thermal performance paper) (retrieved Oct 2026)
  57. Oak Ridge National Laboratory, Christian, Kosny, Desjarlais, Childs (ORNL): 'The Whole-Wall Thermal Performance Calculator—On the Net' (Thermal Envelopes VII, c.1998) (retrieved Oct 2026)
  58. U.S. DOE Building America Solution Center (PNNL), DOE Building America Solution Center RED Calc: Parallel Path R-Value tool (PNNL) (retrieved Oct 2026)
  59. City of Seattle SDCI (reproduction of ICC 2021 IRC), 2021 Seattle Residential Code, Chapter 3 Building Planning (retrieved Oct 2026)
  60. Federal Trade Commission (eCFR), 16 CFR Part 460 (FTC R-value Rule), eCFR up to date as of 10/08/2026 (retrieved Oct 2026)
  61. US EPA ENERGY STAR, ENERGY STAR 'Why Seal and Insulate?' (retrieved Oct 2026)
  62. US EPA ENERGY STAR, ENERGY STAR 'Methodology for Estimated Energy Savings' (retrieved Oct 2026)
  63. U.S. EPA ENERGY STAR, ENERGY STAR Seal and Insulate page (retrieved Oct 2026)
  64. Oak Ridge National Laboratory (Christian, Kosny, Desjarlais, Childs), The Whole Wall Thermal Performance Calculator — On the Net, Thermal Envelopes VII (1998) (retrieved Oct 2026)
  65. US Navy Civil Engineering Laboratory (contract N68305-77C-0009; work by Johns-Manville R&D Center, D. Verschoor), Effectiveness of Building Insulation Applications (Nov 1977), DTIC ADA053452 (retrieved Oct 2026)
  66. BRANZ (New Zealand building research levy-funded institute), Poorly fitted wall insulation cuts thermal performance, BUILD 117 (Apr/May 2010), I. Cox-Smith (retrieved Oct 2026)
  67. City of Owatonna, MN Building Department, City of Owatonna (MN) Building Department: Characteristics of Building Materials (Jan 28, 2009) (retrieved Oct 2026)
  68. US Federal Trade Commission (16 CFR 460), 16 CFR Part 460 Labeling and Advertising of Home Insulation (FTC R-value Rule), via Cornell LII e-CFR mirror - § part-460 (retrieved Oct 2026)
  69. National Roofing Contractors Association (NRCA), Professional Roofing, Tech Today, Mark S. Graham, Professional Roofing, March 2015 ('NRCA tests reveal polyisocyanurate R-values are lower than product manufacturers' published long-term thermal resistance values') (retrieved Nov 2026)
  70. Building Science Corporation, Info-502: Temperature Dependence of R-values in Polyisocyanurate Roof Insulation (effective 2013-04-12) (retrieved Oct 2026)
  71. ROCKWOOL Building Science (with RDH), Temperature Dependence of Aged Polyisocyanurate Insulation R-values — Research Summary (2017-09-13) (retrieved Oct 2026)
  72. Owens Corning, Product Data Sheet FOAMULAR NGX Insulating Sheathing XPS Insulation, Pub. No. 23512-P, Oct 2025 (retrieved Oct 2026)
  73. Owens Corning Foam Insulation, LLC, Capturing the Thermal Performance of FOAMULAR NGX XPS vs. Polyisocyanurate, Tech Bulletin Pub. No. 10019949-B, July 2026 (retrieved Oct 2026)
  74. National Bureau of Standards (NIST), NBSIR 81-1640 Effective Thermal Conductivity of a Glass Fiberblanket Standard Reference Material (Smith, Hust, Van Poolen, Feb 1981) (retrieved Oct 2026)
  75. Johns Manville, Convection in Fibrous Attic Insulation, Technical Bulletin IST09-005 (Apr 15, 2009) — structuretech.com copy (retrieved Oct 2026)
  76. Oak Ridge National Laboratory (T. Stovall), Closed Cell Foam Insulation: A Review of Long Term Thermal Performance Research, ORNL/TM-2012/583, Nov 2012 (retrieved Oct 2026)
  77. Atlas Molded Products (division of Atlas Roofing Corp.), ThermalStar X Tech Data sheet (ARC-064 TS X Tech-Data_10.25) (retrieved Nov 2026)
  78. US Federal Trade Commission (16 CFR 460), 16 CFR Part 460 Labeling and Advertising of Home Insulation (FTC R-value Rule), via Cornell LII e-CFR mirror - § 460.12 (retrieved Oct 2026)