Insulation R-Value Charts & Guides

Code requirements, material data, and calculators for every project.

Attic: the 2021 IECC asks for R-30 to R-60
Less heat escapingMore heat escapingIllustration of a winter thermal scan, not a measurement.

What Is R-Value in Insulation?

R-value measures thermal resistance, the ability of insulation to resist heat flow. The higher the R-value, the greater the insulating effectiveness.[1][2][3] R-value is expressed as h·ft²·°F/BTU in the United States, representing the temperature difference needed to transfer one BTU of heat per hour through one square foot of material.[4]

The R-value you need depends on three factors: your climate zone (determined by heating and cooling degree days), the location being insulated (attic, walls, basement, etc.), and local building codes. The International Energy Conservation Code (IECC) establishes minimum R-value requirements, though many energy-conscious homeowners exceed these minimums for better comfort and energy savings.

R-values are additive when materials are layered. For example, R-19 fiberglass batts plus R-11 batts equals R-30 total. However, compression reduces R-value—a compressed R-19 batt performs below its rated value. Proper installation without compression, gaps, or voids is essential for achieving rated performance.[5][6]

R-Value Insulation Chart

This chart shows R-value per inch and typical applications for common insulation materials. Installed costs are in the cost guide below.

  • Closed-cell spray foamR-6.0 – R-7.0
  • Polyiso boardR-5.6 – R-6.5
  • XPS boardR-5.0
  • EPS boardR-3.6 – R-4.4
  • Open-cell spray foamR-3.5 – R-3.8
  • Mineral woolR-3.7 – R-4.3
  • Fiberglass battsR-3.0 – R-4.3
  • Blown-in fiberglassR-2.5 – R-3.0
  • Blown-in celluloseR-3.2 – R-3.8
Labeled R-value per inch at the FTC test temperature, from the cited table on this page. Bar colors follow the thermal scan: cooler means more R per inch.
MaterialR-Value/InchBest ForDIY?
Closed-Cell Spray FoamR-6.0 – R-7.0Rim joists, crawl spaces, moisture barriersNo
Polyisocyanurate (Polyiso)R-5.6 – R-6.5Exterior sheathing, roofing, continuous insulationYes
Extruded Polystyrene (XPS)R-5.0Below-grade, foundation, high-moisture areasYes
Expanded Polystyrene (EPS)R-3.6 – R-4.4ICF walls, EIFS, cost-effective rigid foamYes
Open-Cell Spray FoamR-3.5 – R-3.8Interior walls, sound control, cathedral ceilingsNo
Mineral Wool (Rockwool)R-3.7 – R-4.3Fire resistance, soundproofing, exterior wallsYes
Fiberglass BattsR-3.0 – R-4.3Standard wall cavities, attics, floorsYes
Blown-In FiberglassR-2.5 – R-3.0Attic floors, wall retrofitsYes*
Cellulose (Blown-In)R-3.2 – R-3.8Attics, dense-pack walls, retrofitsYes*
Radiant BarrierN/A**Attic rafters (hot climates only)Yes

*Blower machine rental available at home improvement stores. **Radiant barriers reduce radiant heat transfer and have no standalone R-value; under the FTC rule, a reflective product's R-value depends on the adjacent air space and heat-flow direction, not an ASTM C518 test of the foil. FSEC research puts the saving at 8–12% of annual cooling costs in the Southeast, a range DOE's Building America program repeats for hot climates.[32][33][34][1][31]

Per-inch R-values: spray foam from manufacturer and ICC-ES evaluation reports; rigid boards (polyiso, XPS, EPS) from manufacturer data sheets; mineral wool from ROCKWOOL ComfortBatt and ComfortBoard technical data; fiberglass batts, blown fiberglass and cellulose from manufacturer submittal sheets and the FTC 16 CFR 460 test basis (75°F mean). Values are clear-material R per inch, not whole-wall assembly values.[7][8][9][10][18][11][12][13][14][15][16][17][19][20][21][22][23][24][25][26][27][28][29]

2021 IECC Insulation Requirements by Climate Zone

The International Energy Conservation Code (IECC) establishes minimum R-value requirements based on climate zone. These are legal minimums—exceeding them improves energy efficiency and comfort. Use our R-Value Calculator to find your zone by ZIP code.

ZoneCeiling/AtticWood Frame WallFloorBasement WallCrawl Space
Zone 1R-30R-13 or R-0+10ciR-13NRNR
Zone 2R-49R-13 or R-0+10ciR-13NRNR
Zone 3R-49R-20 or R-13+5ci or R-0+15ciR-19R-5ci or R-13R-5ci or R-13
Zone 4 (except Marine)R-60R-30 or R-20+5ci or R-13+10ci or R-0+20ciR-19R-10ci or R-13R-10ci or R-13
Zone 4 MarineR-60R-30 or R-20+5ci or R-13+10ci or R-0+20ciR-30R-15ci or R-19 or R-13+5ciR-15ci or R-19 or R-13+5ci
Zone 5R-60R-30 or R-20+5ci or R-13+10ci or R-0+20ciR-30R-15ci or R-19 or R-13+5ciR-15ci or R-19 or R-13+5ci
Zone 6R-60R-30 or R-20+5ci or R-13+10ci or R-0+20ciR-30R-15ci or R-19 or R-13+5ciR-15ci or R-19 or R-13+5ci
Zone 7R-60R-30 or R-20+5ci or R-13+10ci or R-0+20ciR-38R-15ci or R-19 or R-13+5ciR-15ci or R-19 or R-13+5ci
Zone 8R-60R-30 or R-20+5ci or R-13+10ci or R-0+20ciR-38R-15ci or R-19 or R-13+5ciR-15ci or R-19 or R-13+5ci

"ci" = continuous insulation (uninterrupted by framing). R-13+5ci means R-13 cavity insulation plus R-5 continuous exterior insulation. "NR" = Not Required by code. Source: 2021 IECC Table R402.1.3, residential prescriptive R-value path. Local codes may differ—always verify with your building department.[35][36]

These are 2021 IECC values. The 2024 IECC is the current model edition (DOE final determination, 30 December 2024). The 2024 edition lowers the ceiling minimum to R-30 in Zones 0–1, R-38 in Zones 2–3 and R-49 in Zones 4–8, adds an above-deck roof row (R-25ci/R-30ci/R-35ci) and floor continuous-insulation options; the wall, basement and crawl values above are unchanged in 2024. State adoption varies.[37][38]

R-Value Per Inch Comparison

R-value per inch determines how much thickness you need to achieve your target R-value. Higher R-per-inch materials achieve the same thermal resistance in less space—critical for walls with limited cavity depth or cathedral ceilings where every inch matters.

Material, highest R per inch firstR/Inch (75°F label)
Closed-Cell Spray FoamR-6.0 – R-7.0
Polyisocyanurate (Polyiso)R-5.6 – R-6.5
Extruded Polystyrene (XPS)R-5.0
Expanded Polystyrene (EPS)R-3.6 – R-4.4
Mineral Wool (Rockwool)R-3.7 – R-4.3
Open-Cell Spray FoamR-3.5 – R-3.8
Cellulose (Blown)R-3.2 – R-3.8
Fiberglass BattsR-3.0 – R-4.3
Blown-In FiberglassR-2.5 – R-3.0

The same per-inch ranges as the R-value chart above, from the same sources: spray foam from ICC-ES evaluation reports, boards from manufacturer data sheets, fibrous materials from the makers' product sheets.[7][9][18][11][14][17][19][23][29][24]

Thickness Required for R-49 Attic Insulation

Closed-Cell Foam7–8.2 inches
Cellulose13.3–14.5 inches
Fiberglass Batts13.5–14 inches (one R-49 batt)
Blown Fiberglass16.4–18.25 inches

Cellulose and blown fiberglass depths are the makers' settled minimums for R-49; closed-cell depth is R-49 divided by R-6.0 to R-7.0 per inch. A single R-49 fiberglass batt is 13.5 to 14 inches; two stacked standard batts (R-30 + R-19) run 15.75 to 16.75 inches. Follow the coverage chart on the bag or batt you buy.[23][25][24][7][29][30][22]

IECC Climate Zones Explained

The United States is divided into 8 climate zones, Zone 1 the hottest and Zone 8 the coldest. The IECC defines Zones 3–8 by heating degree days to a 65°F base (HDD65) and Zones 0–2 by cooling degree days to a 50°F base (Table R301.3). Your zone sets the minimum insulation requirements. Note that 41 of 50 states contain more than one climate zone.[39][42][43]

ZoneDefined by (Table R301.3)Example citiesCeiling (2021 IECC)Wood-frame wall (2021 IECC)
19,000 < CDD50°F < 10,800Honolulu HI (1A), Miami FL (1A)R-30R-13or R-0+10ci
26,300 < CDD50°F ≤ 9,000Austin TX (2A), Phoenix AZ (2B), Dallas TX (2A)R-49R-13or R-0+10ci
3CDD50°F ≤ 6,300 and HDD65°F ≤ 3,600Atlanta GA (3A), El Paso TX (3B), San Francisco CA (3C)R-49R-20or R-13+5cior R-0+15ci
4CDD50°F ≤ 6,300 and 3,600 < HDD65°F ≤ 5,400Baltimore MD (4A), Albuquerque NM (4B), Portland OR (4C)R-60R-30or R-20+5cior R-13+10cior R-0+20ci
5CDD50°F < 6,300 and 5,400 < HDD65°F ≤ 7,200Boston MA (5A), Boise ID (5B), Buffalo NY (5A)R-60R-30or R-20+5cior R-13+10cior R-0+20ci
67,200 < HDD65°F ≤ 9,000Bismarck ND (6A), Helena MT (6B), Burlington VT (6A)R-60R-30or R-20+5cior R-13+10cior R-0+20ci
79,000 < HDD65°F ≤ 12,600Anchorage AK (7)R-60R-30or R-20+5cior R-13+10cior R-0+20ci
812,600 < HDD65°FFairbanks AK (8)R-60R-30or R-20+5cior R-13+10cior R-0+20ci

Example cities and their zones come from PNNL's county climate zone data for the 2021 and 2024 IECC map; the criteria from 2021 IECC Table R301.3; the minimums from 2021 IECC Table R402.1.3, where Marine 4 (4C) uses the zone 5 column. The 2024 IECC lowers the ceiling minimums and keeps the wall values.[52][39][35][38]

Insulation Cost Guide

Installed costs from NREL's Residential Efficiency Measures Database (REMDB 2024): a contractor's price for labor and material, in 2023 dollars, national, per square foot of the surface insulated. REMDB prices insulation by form and place, not by brand or fiber, and has no DIY, removal or minimum-fee rows.[53]

ProjectR-valuePer sq ft (10th–90th percentile)For 1,000 sq ft (median)
Attic floor: blown-in loose fill, fiberglass or cellulose (existing home)R-49$1.02–$2.13$1,017–$2,131 (median $1,825)
Attic floor: batts (existing home)R-49$2.71–$5.11$2,712–$5,108 (median $3,372)
Attic roof deck: open-cell spray foam (existing home)R-21$4.09–$11.32$4,089–$11,316 (median $7,309)
Attic roof deck: closed-cell spray foam (existing home)R-29$7.80–$23.04$7,799–$23,045 (median $11,258)
Stud walls: batts (new construction)R-13$1.16–$2.80$1,156–$2,800 (median $1,366)
Wall sheathing: XPS board (new construction)R-5$1.14–$4.31$1,139–$4,305 (median $1,434)
Basement walls, unfinished: XPS board (existing home)R-15$2.45–$6.66$2,446–$6,660 (median $3,259)
Crawl space walls: closed-cell spray foam (existing home)R-15$4.03–$11.92$4,034–$11,918 (median $5,842)
Rim joist: XPS board (existing home)R-10$1.83–$5.52$1,828–$5,518 (median $2,381)

REMDB 2024 has no spray foam row for rim joists, so the rim-joist row is XPS board. Get quotes for your own area; the calculator below prices any area and R-value REMDB covers.[53]

Insulation Installation Guides

Proper installation is as important as choosing the right material. Installation defects measurably cut performance: a "worst typical" batt install in a 2x6 R-19 wall tested about 14% below a perfect install in ORNL hot-box work, and small gaps or uninsulated areas can cut a wall or ceiling's R-value by a third or more. Our guides cover both DIY projects and what to expect from professional installation.[44][45][46]

Attic Insulation

Air sealing, vapor barriers, ventilation baffles, and achieving R-49 or higher. Covers blown-in, batts, and spray foam options.

Read guide

Wall Insulation

New construction vs. retrofit approaches. Dense-pack cellulose, drill-and-fill, and continuous exterior insulation strategies.

Read guide

Basement Insulation

Interior vs. exterior approaches, moisture management, rim joist air sealing, and meeting code for conditioned basements.

Read guide

Crawl Space Insulation

Encapsulation vs. vented crawl spaces, vapor barriers, and choosing between floor insulation and crawl space wall insulation.

Read guide

Garage Insulation

Insulating attached garage walls, ceilings above living space, and garage doors for improved comfort and energy savings.

Read guide

How to Install Blown-In

Step-by-step DIY guide for blown-in fiberglass and cellulose. Equipment rental, safety, and achieving consistent depth.

Read guide

Insulation Material Comparisons

These side-by-side comparisons analyze cost, performance, installation requirements, and best applications for each material pairing.

Frequently Asked Questions

What R-value do I need for my attic?

The minimum R-value for attics depends on your climate zone. Zone 1 requires R-30, Zones 2-3 require R-49, and Zones 4-8 require R-60 per the 2021 IECC (Table R402.1.3). On the prescriptive R-value path, the IECC allows R-49 over 100% of the ceiling area to satisfy R-60 if the full uncompressed R-49 extends over the wall top plates at the eaves. The 2024 IECC drops the ceiling minimum to R-49 in Zones 4-8 and removes this R-60 clause. Use our R-Value Calculator to find the specific requirement for your ZIP code.[35][37]

How thick should my insulation be?

Thickness depends on the material's R-value per inch and your target R-value. For R-49 attic insulation: blown fiberglass needs about 16.5-18 inches, cellulose needs 14 inches, and closed-cell spray foam needs only 7.5 inches. Use our Thickness Calculator to determine exact depth for any R-value and material combination.[24][29][8]

What is the best insulation for walls?

For new construction, fiberglass or mineral wool batts sized to your wall cavity are most common: R-13 or R-15 for 2x4, and a 5.5-inch R-21 (or R-23 mineral wool) batt for 2x6. An R-19 batt compressed into a 2x6 cavity delivers only about R-18, so pick a 5.5-inch product for the full rating. Add continuous exterior insulation (rigid foam or mineral wool boards) to reduce thermal bridging. For retrofits without removing drywall, blown-in cellulose or fiberglass via small holes is the standard approach. Spray foam offers the best air sealing but costs 2-3x more. See our Wall Insulation Guide for detailed recommendations.[47][22][28][48]

Is spray foam worth the extra cost?

Spray foam provides the highest R-value per inch (R-6.5 for closed-cell) and creates an air barrier, eliminating the need for separate air sealing. It's worth the extra cost for rim joists, crawl spaces, cathedral ceilings, and anywhere air sealing is critical. For standard attics with accessible air sealing, blown-in cellulose or fiberglass often provides better ROI. See our spray foam cost analysis for payback calculations.

Do I need a vapor barrier with insulation?

It depends on climate and location. In cold and very cold climates (Zones 5-8 and Marine 4), the IRC requires a Class I or II vapor retarder on the warm-in-winter (interior) side of frame walls; kraft facing is a Class II retarder. Zone 4 except Marine permits Class III, and Zones 1-2 keep vapor-open assemblies so moisture can dry toward the interior. Never sandwich insulation between two vapor barriers: moisture must be able to dry in at least one direction. See our faced vs. unfaced guide for details.[49]

Can I add insulation on top of existing insulation?

Yes, adding insulation over existing material is common practice for attic upgrades. The new insulation does not need a vapor retarder; only the bottom layer should have one. Ensure the existing insulation is dry and not compressed. If upgrading from R-19 to R-49, you're adding R-30 worth of material. Blown-in products work best for layering over existing batts. Address any air leaks before adding insulation for maximum effectiveness.

What's the difference between R-value and U-value?

R-value measures thermal resistance (higher is better), while U-value measures thermal conductance (lower is better). They are reciprocals: U = 1/R. R-value is used for insulation materials in the US, while U-value is often used for windows and whole-assembly performance. An R-20 wall assembly has a U-value of 0.05. The IECC code specifies both, with U-values used for windows and doors.[5][4][35]

How much can I save by adding insulation?

Savings depend on your current insulation level, target level, climate, and energy costs. Air sealing plus adding insulation saves an average of about 15% on heating and cooling costs, roughly 7-20% depending on climate zone, per EPA ENERGY STAR. For 1,000 sq ft of attic floor in an existing home, NREL's REMDB 2024 prices R-49 of blown-in loose fill at $1,017–$2,131 (median $1,825) installed, in 2023 dollars. Use our Savings Calculator for a personalized estimate.[50][51][53]

Insulation Calculators & Tools

Free interactive tools to help you determine requirements, estimate costs, and choose the right insulation for your project.

Sources

  1. Federal Trade Commission (eCFR), 16 CFR Part 460 (FTC R-value Rule), eCFR up to date as of 10/08/2026 (retrieved Oct 2026)
  2. US Federal Trade Commission (16 CFR 460), 16 CFR Part 460 Labeling and Advertising of Home Insulation (FTC R-value Rule), via Cornell LII e-CFR mirror - § 460.12 (retrieved Oct 2026)
  3. US EPA ENERGY STAR, ENERGY STAR (US EPA) 'Recommended Home Insulation R-Values' - Recommended insulation levels for retrofitting existing wood-framed buildings (retrieved Oct 2026)
  4. NIST, NIST Guide to the SI (SP 811), Appendix B.9 Factors for units listed by kind of quantity (retrieved Oct 2026)
  5. ASHRAE / ANSI / IES, ANSI/ASHRAE/IES Addendum ay to Standard 90.1-2022 (approved 2024-10-31), Normative Appendix A sec. A3.4.1 (retrieved Oct 2026)
  6. Natural Resources Canada (Government of Canada), NRCan, Tables for Calculating Effective Thermal Resistance of Opaque Assemblies (ENERGY STAR for New Homes; issued 2014-01-02, modified 2025-01-14) (retrieved Oct 2026)
  7. ICC Evaluation Service (holder: Huntsman Building Solutions, LLC), ICC-ES Evaluation Report ESR-4073 (Heatlok HFO High Lift (closed-cell, HFO)), reissued Aug 2026 (retrieved Oct 2026)
  8. ICC Evaluation Service (holder: Huntsman Building Solutions, LLC), ICC-ES Evaluation Report ESR-2629 (Foam-Lok FL2000 (closed-cell; aka Air Tight CC, GuardFoam 55 CC, Foam-Lok AB2000)), reissued Dec 2021, revised Jul 2022 (copy on huntsmanbuildingsolutions.com) (retrieved Oct 2026)
  9. ICC Evaluation Service (holder: Huntsman Building Solutions LLC), ICC-ES Evaluation Report ESR-1826 (Classic Ultra Select (also Classic, Classic Ultra) open-cell), reissued Mar 2026 (renewal Feb 2027) (retrieved Oct 2026)
  10. ICC Evaluation Service (holder: Huntsman Building Solutions, LLC), ICC-ES Evaluation Report ESR-2847 (Foam-LOK FL500 (aka AirTight OC, GUARDFOAM 55 OC, Open Cell Retrofit Foam) open-cell), reissued Sep 2026 (retrieved Oct 2026)
  11. NRCA, Professional Roofing, 'PIMA updates its QualityMark CM program for determining long-term thermal resistance', Mark S. Graham (NRCA), Professional Roofing, Aug 2013 (Tech Today) (retrieved Nov 2026)
  12. Polyisocyanurate Insulation Manufacturers Association (PIMA), PIMA Performance Bulletin #04 'Measuring the R-value of Polyiso Roof Insulation' (footer 5/14; cites 2015 data) (retrieved Oct 2026)
  13. Rmax, Rmax Product Data Sheet THERMASHEATH (foil-faced polyiso), Revision 05-15-2025 (retrieved Nov 2026)
  14. Owens Corning Foam Insulation, LLC, FOAMULAR & FOAMULAR NGX XPS Insulation: ASTM C578 Types and Physical Properties (Tech Bulletin, Pub. No. 10015702-C, July 2025) reproducing ASTM C578-23 (retrieved Oct 2026)
  15. DuPont (Performance Building Solutions), Styrofoam Brand Square Edge Extruded Polystyrene Foam Insulation product page (retrieved Oct 2026)
  16. Kingspan Insulation LLC, Kingspan GreenGuard GG25-LG XPS Insulation Board product data sheet, v3, 03/2026 (retrieved Nov 2026)
  17. Atlas Molded Products (division of Atlas Roofing Corp.), ThermalStar E Tech Data sheet (ARC-064 TS E Tech-Data_10.25) (retrieved Nov 2026)
  18. ICC Evaluation Service (holder: SOPREMA Corporation), ICC-ES Evaluation Report ESR-4411 (SOPRA-SPF 201 (closed-cell)), reissued May 2021 (renewal May 2023) (retrieved Oct 2026)
  19. ROCKWOOL, ROCKWOOL Comfortbatt Thermal Batt Insulation Technical Data Sheet (US), issued 07-2026 (retrieved Oct 2026)
  20. ROCKWOOL, ROCKWOOL Comfortboard 80 Exterior Continuous Insulation TDS, issued 07-2025 (retrieved Oct 2026)
  21. ROCKWOOL, ROCKWOOL Comfortboard 110 Exterior Continuous Insulation TDS, issued 01-2025 (retrieved Oct 2026)
  22. Johns Manville, Fiberglass Manufacturers Fact Sheet (BID-380, 12/19, (c)2019) (retrieved Oct 2026)
  23. Owens Corning, PINK Next Gen Fiberglas Insulation Manufacturers Fact Sheet (Pub. 10025109-B, May 2026) (retrieved Oct 2026)
  24. Owens Corning, ProPink L77 PINK Fiberglas Loosefill Insulation Manufacturers Fact Sheet (Pub. 22676-O, Dec 2023) (retrieved Oct 2026)
  25. Johns Manville, JM Building Insulation Submittal Form (BID-0028, 9/26) (retrieved Oct 2026)
  26. Knauf Insulation, Knauf Jet Stream ULTRA Blowing Insulation Product Data Sheet (valid from 05/25; (c)2024), linked from knaufnorthamerica.com product page (retrieved Oct 2026)
  27. CertainTeed, CertainTeed InsulSafe SP Fiberglass Blowing Insulation data sheet (Code No. 09-11-4525-US-EN, 10/24) (retrieved Nov 2026)
  28. City of Seattle SDCI (adopts WA State Energy Code App. A), 2021 Seattle Energy Code, Appendix A (Default Heat Loss Coefficients), Table A101.4 R-value of fiberglass batts compressed within various depth cavities (retrieved Oct 2026)
  29. Applegate Insulation (Greenfiber), Applegate Loose-fill Cellulose Insulation Fact Sheet (#IFS-ALF26.5-201606-A, (c)2020; RDS-LF9587), archived copy (Wayback Machine 2023-05-25) (retrieved Nov 2026)
  30. Greenfiber, Greenfiber SANCTUARY Defense Attic Card (PM-6.3328-SD Rev C, 03/25) (retrieved Nov 2026)
  31. US Federal Trade Commission (16 CFR 460), 16 CFR Part 460 Labeling and Advertising of Home Insulation (FTC R-value Rule), via Cornell LII e-CFR mirror - § 460.5 (retrieved Oct 2026)
  32. Florida Solar Energy Center (UCF), FSEC-EN-15 'Radiant Barriers: A Question and Answer Primer' (I. Melody; rev. P. Fairey, D. Beal; ©2005) (retrieved Oct 2026)
  33. U.S. DOE Building America (PNNL), Building America Energy Performance Brief: Installing a Radiant Barrier in the Attic (PNNL-SA-83945, Oct 2011) (retrieved Oct 2026)
  34. Oak Ridge National Laboratory, ORNL Radiant Barrier Fact Sheet: 'Effect of Radiant Barriers on Heating and Cooling Bills' (DOE/ORNL; page undated, legacy fact sheet) (retrieved Oct 2026)
  35. International Code Council (ICC), 2021 IECC Errata (complete) - Table R402.1.3 entry, Printings: All, posted 2021-08-10 updated 2026-09-18 (retrieved Oct 2026)
  36. US DOE Building America Solution Center (PNNL), DOE/PNNL Building America Solution Center: '2009-2021 IECC and IRC Minimum Insulation Requirements for New Homes' (updated 2021-09-17) (retrieved Oct 2026)
  37. US DOE (Federal Register), Final Determination Regarding Energy Efficiency Improvements in the 2024 IECC, 89 FR 106458, 2024-12-30, docket EERE-2024-BT-DET-0007 (retrieved Oct 2026)
  38. International Code Council (ICC) - reproduced by Virginia DHCD, Virginia DHCD 2024 code development cycle, Energy Sub-Workgroup agenda 2025-11-14; proposal REC-R402.1.3-24 (HBAV) reproduces 2024 IECC Table R402.1.3 as its base text (retrieved Oct 2026)
  39. International Code Council (ICC), 2021 IECC Code and Commentary - Chapter 3 [CE] sample (3810S21 Sample PDF) (retrieved Oct 2026)
  40. International Code Council (ICC) / State of Colorado model code, Colorado Model Low Energy and Carbon Code - ICC sample excerpt (3800S24CO Sample PDF), Table C301.1 'Climate Zones, Moisture Regimes and Warm Humid Designations by State, County and Territory' (pp. 36-66, all 50 states + DC + territories) (retrieved Oct 2026)
  41. International Code Council (ICC), 2024 IECC Code and Commentary - sample chapter (3560S24 Sample PDF) (retrieved Oct 2026)
  42. PNNL for US DOE, Methodology for Evaluating Residential Energy Code Updates, PNNL-37098 (Dec 2024) (retrieved Oct 2026)
  43. PNNL for US DOE, National Cost Effectiveness of the Residential Provisions of the 2021 IECC, PNNL-31019 (June 2021), DOE OSTI copy (retrieved Nov 2026)
  44. Oak Ridge National Laboratory (Christian, Kosny, Desjarlais, Childs), The Whole Wall Thermal Performance Calculator — On the Net, Thermal Envelopes VII (1998) (retrieved Oct 2026)
  45. US Navy Civil Engineering Laboratory (contract N68305-77C-0009; work by Johns-Manville R&D Center, D. Verschoor), Effectiveness of Building Insulation Applications (Nov 1977), DTIC ADA053452 (retrieved Oct 2026)
  46. BRANZ (New Zealand building research levy-funded institute), Poorly fitted wall insulation cuts thermal performance, BUILD 117 (Apr/May 2010), I. Cox-Smith (retrieved Oct 2026)
  47. Owens Corning, PINK Next Gen Fiberglas Insulation Product Data Sheet (Pub. 10024567-J, May 2026) (retrieved Oct 2026)
  48. NAIMA, Insulation Facts #21: High-Performance Batts for Walls and Cathedral Ceilings (BI 467, 7/04) (retrieved Oct 2026)
  49. City of Seattle SDCI (reproduction of ICC 2021 IRC), 2021 Seattle Residential Code, Chapter 7 Wall Covering (retrieved Oct 2026)
  50. US EPA ENERGY STAR, ENERGY STAR 'Why Seal and Insulate?' (retrieved Oct 2026)
  51. US EPA ENERGY STAR, ENERGY STAR 'Methodology for Estimated Energy Savings' (retrieved Oct 2026)
  52. Pacific Northwest National Laboratory (PNNL) for US DOE Building America, Guide to Determining Climate Zone by County: Building America and IECC 2021 Updates — county climate zone data files (ClimateZoneDataFiles.zip, ClimateZones shapefile, 2022-08-02) (retrieved Oct 2026)
  53. National Renewable Energy Laboratory (NREL), National Residential Efficiency Measures Database (REMDB) 2024 — machine-readable file REMDB_2024.12.23.xlsx (CC BY 4.0) (retrieved Oct 2026)

Independent Resource: InsulationRValues.com is not affiliated with any manufacturer, retailer, or installation company. Our recommendations are based on building science data from the U.S. Department of Energy, Oak Ridge National Laboratory, Building Science Corporation, and IECC building codes.

Compiled by Marko Visic. Last updated November 17, 2026.